skip to main content
Language:
Search Limited to: Search Limited to: Resource type Show Results with: Show Results with: Search type Index

Estimation of energy-saving potential and indoor thermal comfort by the central control of the heating curve in old apartment buildings

E3S Web of Conferences, 2021, Vol.246, p.9002 [Peer Reviewed Journal]

2021. This work is licensed under https://creativecommons.org/licenses/by/4.0/ (the “License”). Notwithstanding the ProQuest Terms and conditions, you may use this content in accordance with the terms of the License. ;ISSN: 2267-1242 ;ISSN: 2555-0403 ;EISSN: 2267-1242 ;DOI: 10.1051/e3sconf/202124609002

Full text available

Citations Cited by
  • Title:
    Estimation of energy-saving potential and indoor thermal comfort by the central control of the heating curve in old apartment buildings
  • Author: Hajian, Hatef ; Ahmed, Kaiser ; Kurnitski, Jarek
  • Thalfeldt, M. ; Kurnitski, J.
  • Subjects: Air flow ; Air temperature ; Apartment buildings ; Apartments ; Buildings ; Energy ; Energy conservation ; Flow rates ; Heat ; Heat loss ; Low temperature ; Residential areas ; Space heating ; Thermal comfort ; Thermostats ; Ventilation
  • Is Part Of: E3S Web of Conferences, 2021, Vol.246, p.9002
  • Description: In this research, an existing building calibrated simulation model from 1981 was built based on measured energy and indoor temperature data. The model was used to study the central control's energy-saving potential. With parametric simulations, DHW circulation internal heat gain and ventilation airflow rate was determined as 85% and 0.29 l/s/m², respectively. DHW circulation heat loss has been found almost as high as DHW use. Dropping the heating curve from 70/40 °C to 65/35 °C resulted in a saving of 0.6 kWh/m²a (0.8% of space heating energy) on the cost of thermal comfort as yearly hours of the mean air temperature below 21 °C rose from 2.7% to 9.0%. It was necessary to reduce the heating curve to 55/25 °C in a hypothetical scenario with fully open thermostats, indicating heat redistribution from warmer to colder rooms, leading to higher heating energy. The findings indicate no energy saving potential due to compromising thermal comfort even by 5 °C heating curve reduction. It was revealed that the building average indoor temperature is not a factor to estimate energy-saving potential because of too low temperature in the coldest apartments.
  • Publisher: Les Ulis: EDP Sciences
  • Language: English
  • Identifier: ISSN: 2267-1242
    ISSN: 2555-0403
    EISSN: 2267-1242
    DOI: 10.1051/e3sconf/202124609002
  • Source: EDP Open
    ROAD: Directory of Open Access Scholarly Resources
    ProQuest Central
    DOAJ Directory of Open Access Journals

Searching Remote Databases, Please Wait